LIYY

Place of use

This type of cables are used as signal and data transmission cables in the connections of electronic control systems, sound frequency transmission.

Structure

Inner Conductor

Electrolytic Stranded Annealed Copper Wire, Class 5
EN 60228, IEC 60228, VDE 0295

Insulation

PVC Compound EN 50290-2-21, DIN 47100 Colour Code

Stranding

Cores Twisted in Layers

Seperator

PES Tape

Outer Sheath

PVC Compound EN 50290-2-22, RAL 7032 Grey

 

Product Code Dimension and Weights Electrical Properties
Nominal Cross Section Overall Diemeter
( ~ )
Net Weight
( ~ )
Standart Lenght Max. Dc Conductor Resistance at 20◦ C Current Carrying Capacity
In Ground at 20° C On Air at 30° C

Technical Info


CONDUCTOR 
RESISTANCE
INSULATION
RESISTANCE
MUTUAL 
CAPACITY
CURRENT 
CARRYING 
CAPACITY
OPERATING
VOLTAGE
mm2
0,22
0,34
0,50
0,75
1,0
1,5
2,5
Ω/km
79
56
39
26
19,5
13,3
7,98
MΩxKm
0,22 ve 0,34 mm2 = 200
≥0,50 mm2 = 20
mm2
0,22
0,34
0,50
0,75
1,0
1,5
2,5
pf/m
110
110
120
120
120
120
120
mm2
0,22
0,34
0,50
0,75
1,0
1,5
2,5
A
2,5
4,5
6,0
13
16
20
25
0,22 ve 0,34 mm2 = 250 V
≥0,50 mm2 = 300/500 V
TEST VOLTAGEBENDING 
RADIUS
TEMPERATURE
RANGE
FLAME RETARDANT 
TEST
0,22 ve 0,34 mm2 = 1200 V
≥0,50 mm2 = 2000 V
7,5X D-30ºC+70ºCIEC 60332-1-2
VDE 0482-332-1-2
EN 60332-1-2

Catalog Info